These records cover every 2018 Cummins Power Generation Generator Set. To see whether one car still needs a recall repair, decode its VIN or check it with NHTSA.
Recalls
1 recall names the 2018 Cummins Power Generation Generator Set. Newest first.
Cummins Inc. (Cummins) is recalling certain 2015-2018 Power Generation trailers, models C60D6R, C150D6R, C80D6R, C100D6R, C200D6R, C300D6R, C150D2R3 and C200D2Re, 2016-2018 C275D2Re and 2018 C70D2Re and C100D2Re. These generator sets may have incorrectly wired remote emergency stop and remote start connections causing the remote stop to not function and…
Risk and remedy
Risk
If the unit does not shut down as expected when the remote E-stop is activated, it can increase the risk of injury.
Remedy
Cummins will notify owners, and dealers will inspect the remote E-stop function and, if necessary, repair or replace the remote E-stop/remote start switch panel, free of charge. The recall is expected to begin September 2018. Owners may contact Cummins customer service at 1-800-286-6467.
Technical service bulletins and other communications the manufacturer sent dealers about this vehicle. Ask a dealer for the full document by its number.
10245679This Technical Service Bulletin describes the verification and resolution of issue of Fault codes 3567, 13154, 3559, 13161, 13179, 2976, 4585, 5617 that are shown on display.
10245676This Technical Service Bulletin describes the verification and resolution of issue of some units of Schneider Electric has notified Cummins Inc. that a population of PowerPact L 250-600A Molded Case Circuit Breakers (MCCB) may contain a nonconforming component in the mechanism that may result in the circuit breaker not operating as intended under certain conditions. Cummins Inc. is campaigning these generator sets and transfer switches to implement a Product Notice PRB-233066 issued by Schneider Electric. This is an update to the previously submitted communication.
10245670This Technical Service Bulletin describes the verification and resolution of issue of some units that were approved by customer were short shipped with the DEF level gauge and hour meter.
10144408This Technical Service Bulletin describes the verification and resolution of lifting eye bolts to be under torqued. If they are not in specification, torque to specification per service instructions.
10144407This Technical Service Bulletin is a campaign to replace an old Low Coolant Level (LCL) sensor P/N A042N875 with a new redesigned LCL sensor P/N A059E699 and Service Kit for C100 D2Re P/N A060N209 by all authorized technicians.
10143715This Technial Service Bulletin is a campaign to replace and repair the old Low Coolant Level (LCL) sensor P/N A042N875 with the new re-design LCL sensor P/N A059E699 and service kit for C150 D2Re/C200 D2Re A059R884, C275 D2Re A059R959 by all authorized technicians.
Every Cummins Power Generation Generator Set model year
Bars are owner complaints, dots mark years with recalls. Select a year to open its report.